Indoor Current Limiting Fuse

RN1 Indoor Currenting-limiting Fuse

RN1 Indoor Currenting-limiting Fuse

  • RN1 Indoor Currenting-limiting Fuse

Online Service:

Application
The product is used in overload or short-circuit protection for electric transformer. The current limiting means that the fuse will cut off the circuit before the short-circuit current reaches the peak value.

Melting Characteristics
Current which passes the fuse when being 1.3 times of its specified electric current,Do not fuse for an hour.When the electric furrent through the fuse box is 2times of its specified electric current, fuse in an hour.Refer to its fusing feature curve in chart 1 when seleetthe fuse.

  3 6
20 100 200 300 400 20 75 100 200 300
Max breaking current KV effective vakue 40 20
The mininum breaking current Express with specified electric current multipe Unprovide 1.3 Unprovide 1.3
Three-phase maximum breaking capacity 200                  
Weight 8 8.9 10.8 15.7 15.7 8.5 9.6 13.6 13.6 17
  10 35
  20 50 75 100 200 7.5 10 20 30 40
Max breaking current KV effective vakue 12 3.5
The mininum breaking current Express with specified electric current multipe Unprovide 1.3 Unprovide 1.3
Three-phase maximum breaking capacity 200
Weight 10 11.5 14.5 21 21 10 20 27 27 27

 

Product Type Model Drawing No. Rated Voltage(KA) Rated Current(A) Size
A a L h1 H b
RN1-3/2 RN3 No.3 3 2 220 400 450 125 235 85
RN1-3/3 RN3 3
RN1-3/5 RN3 5
RN1-3/7.5 RN3 7.5
RN1-3/10 RN3 10
RN1-3/15 RN3 15
RN1-3/20 RN3 20
RN1-6/2 RN3 6 2 320 500 550
RN1-6/3 RN3 3
RN1-6/5 RN3 5
RN1-6/7.5 RN3 7.5
RN1-6/10 RN3 10
RN1-6/15 RN3 15
RN1-6/20 RN3 20
RN1-10/2 RN3 10 2 420 600 650
RN1-10/3 RN3 3
RN1-10/5 RN3 5
RN1-10/7.5 RN3 7.5
RN1-10/10 RN3 10
RN1-10/15 RN3 15
RN1-10/20 RN3 20